AUTO-TRANSFORMERS

 


AUTOTRANSFORMERS, YIELD REDUCED SIZE AND COSTS


Frequently, in applications calling for simple voltage step-up or step-down, and where there is no requirement for electrical isolation, applying an autotransformer will result in significant size and weight reductions as well as cost. The power rating of an autotransformer is given by the expression:

    Prated = Pout X (Vhi - Vlow)/Vhi
    Vlow = voltage from lower voltage tap (input or output)
    Vhi = voltage across higher voltage tap (output or input)

STEP UP AUTO-TRANSFORMER



STEP DOWN AUTO-TRANSFORMER